NextStep(DOCS)		Optical Printer Control System		NextStep(DOCS)

    NAME
	NextStep - NextStep micro stepping drives

    NEXTSTEP STATUS LAMPS
    ---------------------
    These drives have four status lamps on the front at the top/left:

        "ON"  - Grn=Legal power, Yel=Shutdown, Red=Overtemp
        "FLT" - Yel=Interlock unconnected, Red=Motor Short
        "BUS" - Yel(Solid)=Overvoltage, Yel(Flash)=Regen, Red=UnderVoltage
       "STEP" - Grn=Incoming Steps (CW), Yel=Incoming Steps (CCW)

    NEXTSTEP DIP SWITCHES
    ---------------------
    The DIP switches along the front of the drive set the power
    and microstepping resolution:

                       (FRONT)
               ┌───────────────────────────┐
               │  NextStep                 │
               │                           │
               │  (ON)  (FLT)              │
               │  (BUS) (STEP)             │
               │                           │
               │    _                      │
               │   (/) AMPS                │
               │    _                      │
               │   (/) AMPS/10             │
               │                           │
               │   () OFFSET A             │
               │                           │
               │   () OFFSET B             │    Drive
               │    _                      │    Resolution  ┌── Switches ──┐
               │   (/) ANTI-RES            │
               │   ┌─────┐                 │    (Standard)  RES1  RES2  RES3
               │ ON│ o-- │  REST           │    ----------  ----  ----  ----
               │   │ o-- │  IDLE           │      5,000     OFF   OFF   ON
               │   │ --o │  WAVEFORM       │     10,000     ON    OFF   ON
               │   │ o-- │  RES 1          │     18,000     OFF   ON    ON
               │   │ --o │  RES 2          │     20,000     ON    ON    ON
               │   │ --o │  RES 3          │     25,000     OFF   OFF   OFF
               │   │ o-- │  LOW/HI mH      │     25,400     ON    OFF   OFF
               │   │ --o │  LOW/HI AntiRes │     36,000     OFF   ON    OFF
               │   └─────┘                 │     50,000     ON    ON    OFF
               │  Industrial Devices Corp. │
               └───────────────────────────┘

     As an example, with SteppersOnline "M0-63-sized" 4.2 amp motors,
     these settings worked fine:

                            REST: ON           AMPS: "2"  \__ together=2.5 amp
                            IDLE: ON        AMPS/10: "5"  /   (low pow setting)
                        WAVEFORM: OFF      ANTI-RES: "8"
                     LOW/HIGH mH: ON
                LOW/HIGH AntiRes: OFF

    NEXTSTEP STEP/DIR WIRING
    ------------------------
    There are 3 optically isolated low voltage inputs: STP/DIR/SD
    There's one optically isolated low voltage output: FLT

    The three inputs are optocoupler inputs with two 100 ohm
    resistors in series as shown here:

                                    100 ohm            ______
                STP  + (/)-----o-----/\/\/-----o----->|      |
                              | |cap          | |cap  | OPTO | --> TO DRIVE
                STP  - (/)-----o-----/\/\/-----o----->|______|
                                    100 ohm

                                    100 ohm            ______
                DIR  + (/)-----o-----/\/\/-----o----->|      |
                              | |cap          | |cap  | OPTO | --> TO DRIVE
                DIR  - (/)-----o-----/\/\/-----o----->|______|
                                    100 ohm

                                    100 ohm            ______
                 SD  + (/)-----o-----/\/\/-----o----->|      |
                              | |cap          | |cap  | OPTO | --> TO DRIVE
                 SD  - (/)-----o-----/\/\/-----o----->|______|
                                    100 ohm

        The one low voltage output is basically the output transistor
        of the optocoupler, when the drive indicates a fault condition.
                                     ______
                FLT  + (/)<---------|      |
                                    | OPTO | <-- FROM DRIVE
                FLT  - (/)<---------|______|

        The input ratings are:
           > 5-15mA @5VDC
           > Setup Time=250nS (min on/off time)

        The output rating:
           > 50mA max, up to 30VDC.
           > Normally conducting.
           > Opens on fault.

        The optocouplers are "HCPL-2631", so you can look up the datasheet
        for the electrical particulars.

    NEXTSTEP MOTOR WIRING
    ---------------------
    It is important that the top and bottom terminal screws labeled "INTLK"
    are wired *together*. Without this, the output amplifier is turned off
    (unlocking the motor) and the "FLT" light will be on. e.g.
                        ______
                INTLK  (/)    |
                   B-  (/)    |
                   B+  (/)    |     Terminal
                  GND  (/)    |      Block
                   A-  (/)    |
                   A+  (/)    |
                INTLK  (/)____|
		        ______|

    The only other wiring needed is to the motor:

        o The B-/B+ to one coil
        o The A-/A+ to other coil

    If you swap the wires for the A pairs, it changes the motor direction.

    If the motor wire has a shield, it can be connected to the GND pin.

    For 4 wire motors, it's simple and you can't really go wrong;
    either you get CW, CCW, or no motor turning. It's not possible
    to "short anything out" if you miswire the four motor coil wires
    to the four A+/A-/B+/B- terminals.

    For 6 wire motors, you can choose between SERIES or PARALLEL wiring;

        o SERIES uses lower power and generates lower heat
        o PARALLEL uses more power and generates more heat
    
    In the following diagram, the '3's are the motor coils,
    and the wire colors are for the IDC motors depicted in the manual.
    See the manual for more information.

    For SERIES wiring (low pow/low heat):

             (B-) ORN ------------.    .------------ RED (A-)
                                  3    3
                                  3    3
                                  3    3
                    .--WHT/ORN ---`    `--- WHT/RED--.
                    |                                |
                    `--WHT/BLK ---.    .--- WHT/YEL--`
                                  3    3
                                  3    3
                                  3    3
             (B+) BLK ------------`    `------------ YEL (A+)



    For PARALLEL wiring (hi pow/hi heat):

             (B-) WHT/BLK ---o--------.   .--------o--- WHT/YEL (A-)
                             |        3   3        |
                            ORN----.  3   3  .----RED
                                   3  3   3  3
                                   3  3   3  3
                                   3  3   3  3
                                   3  3   3  3
                                   3  3   3  3
                          WHT/ORN--`  3   3  `--WHT/RED
                             |        3   3        |
             (B+) WHT/ORN ---o--------`   `--------o--- YEL (A+)


    AUTHOR
        Greg Ercolano / erco@seriss.com / May 14,2024